FIGURING VENTILATION
(use this for ventilation only, cooling formula included below also)
1 AIR CHANGE PER MINUTE OF EXHAUST: STILL WILL GET 4-5 DEGREES TEMPERATURE RISE IN A SMALL GREENHOUSE AND 10 DEGREES IN A LARGER GREENHOUSE WITH THIS FIGURE.
1.) Width x Length x HEIGHT TO EAVE = O
2.) HEIGHT TO RIDGE - HEIGHT TO EAVE = M
3.) M x Width x Length = P 2
4. P + O = CUBIC FEET PER MINUTE
example: 10’ x 10’ greenhouse 1.) 10 x 10 x 6.6 = 660 2.)10’ 4” - 6’ 6” = 3.8 3.) 3.8 X 10 X 10 = 190
2 4.) 190 + 660 = 850 CFM REQUIRED
For Cooling (evap. coolers)
Freestanding Greenhouse: Width (10’) x Length (12’) = 120 Sq. Ft.
Multiply 120 x 15 CFM = 1800 CFM required
Lean-to Greenhouses: Multiply width (6’) x length (10’) = 60 sq. ft.
Multiply height of back wall (9’) x length (10’) = 90 sq. ft. and divide by 2 (90/2) = 45 Sq. ft.
Add 60 Sq. ft and 45 Sq. ft. = 105 Sq. ft
Multiply 105 Sq. ft x 12 CFM = 1260 CFM required
FIGURING VENTILATION
(use this for ventilation only, cooling formula included below also)
1 AIR CHANGE PER MINUTE OF EXHAUST: STILL WILL GET 4-5 DEGREES TEMPERATURE RISE IN A SMALL GREENHOUSE AND 10 DEGREES IN A LARGER GREENHOUSE WITH THIS FIGURE.
1.) Width x Length x HEIGHT TO EAVE = O
2.) HEIGHT TO RIDGE - HEIGHT TO EAVE = M
3.) M x Width x Length = P
2
4. P + O = CUBIC FEET PER MINUTE
example: 10’ x 10’ greenhouse
1.) 10 x 10 x 6.6 = 660
2.)10’ 4” - 6’ 6” = 3.8
3.) 3.8 X 10 X 10 = 190
2
4. 190 + 660 = 850 CFM REQUIRED
For Cooling (evap. coolers)
Freestanding Greenhouse: Width (10’) x Length (12’) = 120 Sq. Ft.
Multiply 120 x 15 CFM = 1800 CFM required
Lean-to Greenhouses: Multiply width (6’) x length (10’) = 60 sq. ft.
Multiply height of back wall (9’) x length (10’) = 90 sq. ft. and divide by 2 (90/2) = 45 Sq. ft.
Add 60 Sq. ft and 45 Sq. ft. = 105 Sq. ft
Multiply 105 Sq. ft x 12 CFM = 1260 CFM required
|